katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

Baxi Bahama 100..No hot water but there is central heating?

Baxi Bahama 100..No hot water but there is central heating?? (it seems that the central heating is working fine)

In addition to that, When the Heating is running, the pressure rises consitently until it reaches 3 bars and I turn it off. When it all cools down, the pressure returns to about 1.2 in the green.Also, I should point out that this only happens when the heating is running. There is no pressure movement when the boiler is dorment, and the hot water feature works fine (with a little pressure drop whilst on).
shiro, November 2009
can this be fixed easy

mark, July 2013
Hi - I have exactly the same problem with my Baxi Bahama 100! Have you found a solution this yet?

Paul, November 2009
expansion vessel needs re-pressurised & dhw flow switch needs replaced

Ian, November 2009
link Click here to see other fixes for Baxi.