T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Click here to ask your question

pressure loss on combi boiler?

I have a baxi combi boiler 105e which loses pressure rapidly can go from 1.5 bar to zero in the space of around forty minutes. Thought it might have been due to leaking glands on radiator but have since been rectified and no longer leaking. There are no obvious signs of leakage and only few drips from warning pipe as usual. Any ideas what could be happening or what i could do as dont want to go pulling up floorboards etc? Any advice would be most appreciated, thank you.
Simon Cochrane, November 2009
thank you chris

simon cochrane, November 2009
has to be a leak. could be a double problem.
expansion vessel needs re charging with air therefore any leak from expansion relief pipe would show a rapid fall in pressure.
or. you WILL have a fairly large leak somewhere. good luck

chris clewett, November 2009