maybe your boiler has a pin holed diaphragm or faulty microswitch on domestic hot water flow switching, usually just fail but can become scaled and a bit hitty missy. get a manual from partsarena.com/baxi and look for water section and microswitch for ideas on location and open hot tap and try making the switch manually with something plastic just in case :-) if it fires when you make the switch try replacing diaphragm.
expansion vessel, big red disc located on back of boiler, if you put your head over the top of boiler and look down next to flue connection to boiler you'll see the red disc has a valve like the ones on your car,
unscrew the cap off and you'll see the pin inside the valve, give it a short press with something thin and observe.
strong blast of air - its fine
weak amount of air - needs recharged
nothing at all - needs recharged
water - its fooked :-)
recharge is- pressure relief valve held open and connect foot pump and pump up to 1 bar, remove foot pump, close pressure relief valve and top up water pressure to 1.5 bar and all should be well.
ste, December 2009