Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

presure at2.5bar all the time ?

worcester28cdirsf presure at 2.5bar all the time wether boiler is on or off, water trickels from relief valve all the time, when boiler is on its hot rustie water tried presure relief valve to reduce to 1bar but it continues to fill to 2.5bar.the fill key is removed it fills withot it in .please can you help
david g., December 2009
water to water heat exchanger is the problem.the plates have separated allowing mains water coming in to mix with heating system.to verify shut off cold water to boiler and reduce pressure to 1bar

plumberterry, December 2009