Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Marc Nollid asked ... Nissan Micra mk 5 2018 rear seat mecanism?    |    Maggie asked ... New Home 535?    |    Click here to ask your question

swiftflow 75?

dhw working ok.not firing up for ch demand
chris d, March 2010
The route of the "please fire up" signal into the boiler is from the timer programmer - to the room thermostat - to the Mid Position Valve on the White wire and from there to the boiler on the Orange wire.

There is conditioning for this signal inside the boiler itself (air pressure switch and overheat stat) but these are OK for Hot Water and may be discounted.

It would be good to have somebody observe / listen to the MPV as you select C/H to come on - it should drive fully over and make a microswitch to send the fire up signal out.

The problem you have is very likely to be caused by either the Timer/Programmer - the Room Thermostat - the Mid Position Valve - very probably the latter.

I have no qualifications or experience with respect to boilers - my advice is next to worthless.

Good luck...

Peccavi, March 2010