Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

i think i may have bleed my heating system incorrectly and now i have no pr?

i think i may have bleed my heating system incorrectly and now i have no pressure reading on my boiler guage.

it is a Potterton suprima 30 - 80
ben, March 2010
I'm assuming this is a combi boiler?.when you bleed the rads the pressure drops.somewhere on the boiler or connected underneath is a filling loop.this needs switching on and you watch the pressure dial and put the water pressure back in to the rad system

A1, March 2010