andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

alpha 240P boiler?

I cannot reduce the pressure on my boiler even after bleeding the radiators, is there something simple I can try before calling in a professional? Or is it completely broken ....
Caroline Thomas, April 2010
filling loop (the bit you use to top the pressure up) may be passing or plate heat exchanger may be burst. try disconnecting the filling loop hose to prove if it's passing, be ready to turn the water mains off in case it is.
if it keeps going up even with the filling loop disconnected then you need a new plate heat exchanger.

Ian, April 2010