Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

Worcester Bosch Greenstar 15Ri fault?

My boiler clicks like mad then goes into fault mode, light off long - light on short!
My engineer is at a loss he has tried/changed everything but he has noticed when it goes into fault mode a spurious 40v appears on the switched live at the boiler?
Mr E, May 2010
my green burner light is not coming on everything else is lit but of course without the burner no start up

stephen, March 2011
capacitor is required on switch live and neutral at boiler

boiler man, May 2010
40v voltage could mean that it may not be the boiler, but a motorised valve, or a jammed/defective gas valve. Your Engineer should have placed a call to Worcester technical dept, they will run through the full test procedure with him over the phone.

Dave, May 2010