GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

boiler is over flowing?

i have a worcester combi oil boiler i filled it up this morning but when i turned off the water feed the gage kept on going up then loads of water started pumping out of what looks like the over flow on the top of the boiler
ken shurmer, May 2010
The pressure gauge normally reads the c.h. system pressure approx 1 to 1.5 bar. The water is coming from your safety valve hopefully being vented outside in a safe manner due to the excess pressure more than 3.5bar. I think that you are unfortunate in as much as when you topped up it coincided with a failure of the flat plate heating exchanger which produces the domestic hot water. Isolate the boiler electrically then shut off mains water to the boiler and vent the system to 1 bar, shut off top-up jumper and disconnect ensure that no open ends are left on the boiler side,gently re-open main water to boiler if pressure gauge dramatically increases then I would conclude that the exchanger is leaking cold water into the heaing cct.

Guytawe, May 2010