Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Vaillant Pro 28. Rads get warm when hot water is run?

I recently had error code F75. Pressure was low and boiler locked out. I put pressure right and turned boiler off then on to clear fault. Hot water now OK, but with CH turned down(Well it is summer now!!) the radiators get warm especially when hot water is being run. Any Ideas please? Installation is about 2 years old.
Geoff R, May 2010
diverter valve is sticking and passing through to radiaters

bob the boiler, May 2010
diverter valve seized, replace part

Mivy Gas Safe, May 2010
I don't know if your boier is the Eco-Tec, if so then I just wonder after your restored the system pressure why it needed to be switched off/on when there is a reset button.Anyhow I believe that you have a 3 way valve problem, why don't you isolate the flow v/v leaving the boiler on the c.h.side to prove this, whilst in the Hot Water mode. I would also just reset the boiler just incase some logic hasn't been reset.

Guytawe, May 2010