3 hours ago Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

loss of pressure?

losing pressure in heating system need to top up twiceaday water coming out of overflow ferolli 77cf combi
stevelin, May 2010
Help us a little Steve,losing pressure at what indicated working pressure?. Normal pressure should be 1-1.5 bar cold if you are venting off at this value then the safety valve, from where the water is coming,is either knackered or there is grit under the seat causing it to pass, it should be set to lift at 3.5bar.

Guytawe, May 2010