Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

What is wrong with the pressure?

Hello

I have a Vokera Linea 24, for the past few months the pressure has been going up to nearly 4 each day.

Have to bleed the radiators morning and night to place back to 1.5.

We have had a part replaced which only cost £20 but that hasn't done anything.

Any help or advice would be much appreciated.

Thanks

Sam
sam, June 2010
expantion vessel is most likely flat or dead. Check / Replace expantion vessel

boilerman, June 2010
Lets logically look at this,you lower the system pressure to 1.5bar,your top-up hose and associated v/vs are shut, the only way mains water can interact with the system pressure is when the internal heating unit exchanges its heat to the domestic hot water this occurs in the flat plate heat exchanger regardless if you have a 3 way valve or a dual pump system in your boiler which swaps the boiler's heated water from its furnace to either CH or DHW. The flat plate exchanger can leak and cause the mains water to leak thro' and over pressurise the system the flat plate is over£100 so I think that hasn't been replaced. When in CH mode the pressure should not significantly rise, turn off the cold feed as an extra check. However if you then go to Hot water demand from your tap check and see if the pressure is now on the rise,turning back on the cold feed first, you can decide your next action on the results.

Guytawe, June 2010