andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

low pressure -filled up and have put too much in ...still very low water fr?

I had v. low water pressure from my taps..looked at the pressure bar which said less then 0.5. so I topped it up with the inlet valve and now it says 3.5 ...still no better pressure ...just a trickle and the overflow pipe outside is now leaking!! Help!
sally, July 2010
You are confusing water pressure with boiler system pressure, you have over-filled the system pressure in your heating system, make sure you have turned off the valves on the filling loop, the pressure relief valve (prv) will continue to leak until the pressure drops below 3 bar and (if you're lucky) you may not have blown the prv, that should then stop leaking.
For future reference, the system pressure should be 1 to 1.5 bar (when the system is cold).

As for your water pressure, I have no idea, you obviously have plenty of cold mains pressure to blow the prv in the first place, maybe an isolation valve in the cold supply to the bolier is restricting the flow?

Carefree, July 2010