2 hours ago Mark asked ... Oven door removal?    |    Jt asked ... Where to buy mt270x petrol cap?    |    Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Click here to ask your question

VUW GB242E no ignition?

The boiler goes through the lighting sequence on heating and water ,all lights on except burner then lock out . some times it will light and after will continue to light but it seems when it is cold it will struggle to light.
I have cleaned the fan venturi.
You hear the pump,fan and pressure switch click but no spark.
stevew, July 2010
cheers will check ,thanks

stevew, July 2010
Fan ventuuri? Blimey! Didn't even know there was one! (Which means you've shot off in the wrong direction).
You state the fan & pump are running, are the switches actually working?
Test the FPS electronically to make sure it it making, also check the pump switch (left of the pump just above) is the microswitch breaking when the pump runs?
1st check: FPS (If the fan is running)
2nd check: PPS (If the pump is running)
Otherwise, it's a pcb fault (relay)
On a 242e/1 it's the left hand pcb
On a 242e/2 it's both pcbs

Check in sequence to save spending unessecary money on pcbs

Carefree, July 2010