Fraser asked ... Spares for power craft ppcs 38cc?    |    FB asked ... Toyota Yaris Speed Camera Warning Beep?    |    Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Click here to ask your question

constant drip?

there is a constant drip from the pressure relief outlet pipe even when the boiler is off. what is theproblem and cure the boiler is a worcester bosch 24cdi .
john macfarlane, August 2010
Is the pressure gauge showing 1bar or 3bar+?
Are you constantly topping up the pressure?
If its staying about 1bar you probably just need to replace the PRV.
If its staying around 3bar all the time this could be the calorifier is pin holed and needs replacing, or an external filling loop is passing(unlikely cos the cdi has an internal loop and key)
If the pressure rises to 3bar when the heating is on this will be the expansion vessel needs recharging. To do this, empty the boiler of pressure via one of the white drain plugs under the boiler and pump up the expansion vessel to roughly 0.75 bar with a normal tyre pump whilst the drain plug is still open...close the drain plug and refill the boiler to 1bar. Hope this helps

gasmanjim, August 2010