probably faulty controls, i.e. timer or room thermostat. it may be a problem with the diverter valve but i doubt it. test the operation of the boiler by holding in the spanner button for 10 seconds, it'll light up, then turn the heating temperature dial to maximum. some lights will start flashing and the boiler will fire up. if your radiators start to heat up then that tells you that the boiler is fine and the problem is with the controls. the boiler will go back to normal after 15 minutes or so. if the rads don't heat then the diverter valve is faulty. if it's the worcester wireless controls you have then check the batteries in the timer.
Ian, August 2010