GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

vaillent 824 6 radiator system?

first five radiators work ok, 6th radiator only gets half hot which runs from the fifth radiator on 15mm pipe, the hot water enter at the top of rad through thermoststat full open air bleed otherside at top, after bleeding the bottom half still cold. have a room wireless thermostat on the far wall from this radiator, the system alway serviced remarks made it takes time for the return system to work fully, my own thoughts air lock or room thermostat problem. please have you come across this type of problem and how to rectify thank you euan
euan, August 2010
no fault with boiler or room stat. either the system needs balanced properly, sludge in radiator or problem with pipework (i.e. 2 rads fed from same pipework)

Ian, August 2010