Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

how can I get central heating working?

vaillant VCW-GB 242 EH recent replacement secondary heat exchanger following leak. Now central heating not working.
May, September 2010
The relationship between HW and CH on this boiler is very critical, you mention having the DHE renewed, this is probably NOT relevant. Assuming all external controls are calling for heat (240v on terminal 4):
When calling for CH does the diverter valve (bottom right of the boiler) make BOTH microswitches? If not, it is probably a problem with the water section/servo valve, the water section can leak through the stuffing box, stopping the servo valve from returning to the CH (rest) position.
1st point to start (assuming 240v on terminal 4)

Carefree, September 2010