Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

baxi 105he?

my boiler works on everything but the shower it turns off half way through the shower and refires after about 10 seconds but doesn't show any faults
sandy, September 2010
my mistake i cleaned the wrong exchanger

sandy, October 2010
tried descaling the heat exchanger it improved the overall ability of my system however i left out quite a big symptom that is the boiler doesnt shut down when the taps are used only when the shower is used the shower is a trevi therm

sandy, October 2010
very easy this one my friend plate heat exchanger blocked with limescale or debris hot water does not get away from the boiler quick enough and sensor kicks in boiler will fire then go out fire then go out repeatedly little tip the het exchangers for the baxi combis are 16 or 24 plate if you need a replacment go for the 24 plate and you will see a vast improvement of your hot water at your taps shower etc drain boiler of dhw turn off cw supply two screws 4 washers ,sometimes you dont need to rplace the washers use same again tighten up refill jobs a good un

byron, October 2010