Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

Glow-worm 12txi driving me mad !?

boiler keeps turning off and displaying f 13 it is also difficult to re light, can anyone please tell me what f13 means please?
steve, September 2010
i had this fault that became more and prevalent until it tripped daily. I noticed that when I disconnected the pump feed (be careful as live!) the realy that switches the pump clicked and the boiler sprung into life. I evetually resoldered the connections for that relay and is now okay. I inspected the baord and there was no obvious dry joints but resoldering seems to have done the trick

eno, December 2010
From the installation manual:

F13 PCB Memory or sensing fault

Loose connections on main PCB or display PCB.
Central heating flow or return thermistor wires unconnected, faulty, trapped.
Electrode ignition leads loose, unconnected, faulty, trapped.
Earthing connection loose, disconnected.

Carefree, September 2010