Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Glow-worm 12txi driving me mad !?

boiler keeps turning off and displaying f 13 it is also difficult to re light, can anyone please tell me what f13 means please?
steve, September 2010
i had this fault that became more and prevalent until it tripped daily. I noticed that when I disconnected the pump feed (be careful as live!) the realy that switches the pump clicked and the boiler sprung into life. I evetually resoldered the connections for that relay and is now okay. I inspected the baord and there was no obvious dry joints but resoldering seems to have done the trick

eno, December 2010
From the installation manual:

F13 PCB Memory or sensing fault

Loose connections on main PCB or display PCB.
Central heating flow or return thermistor wires unconnected, faulty, trapped.
Electrode ignition leads loose, unconnected, faulty, trapped.
Earthing connection loose, disconnected.

Carefree, September 2010
link Click here to see other fixes for Glow-Worm.