thanks for advice got ferroli in changed exspansion valve working like a good en not exspensive either can give number if needed thanx
kelty, November 2010
Addition to answer given, yes it could be over expansion if no air in expansion vessel, also could be dirt in PRV or spring is week
RAWPLUMB, November 2010
check the pressure in the expantion vessel
if water come out of the valve it will need replacing
the presure on the system gauge has to be zero
the pressure in the expantion vessel should be about 1 bar with the pressure in the system at zero
once you have done that represurize system to 1 bar
b, October 2010
edit
I can answer this question...
modena 80e water coming out of external wall pipe?