Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Click here to ask your question

Diameter of vent pipe needed for toilet?

Code calls for 2'' diameter vent pipe, what would happen if only an 1 and a quarter inch pipe were used ?
Thomas, November 2010
you will often find by not fitting or fitting a 1" or smaller vent pipe that the WC will sometimes syhpon the water out when flushed, unless there is a vent pipe fitted elsewhere in the system, it all depends on the design of the pipe work.
JD

JD, November 2010