Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

No hot water when you turn on the tap(Vaillant 242e combi boiler)?

When I turn on the tap for hot water, the boiler does not fire so to overcome this I turned the CH up full to fire the boiler. After some investigation I found that if you make the micro switch manually, on the unit on the right hand side below the pump, the boiler will fire and you have hot water. I was wondering, in the unit I have described is there a diaphragm to operate the micro switch to ignite the boiler. Any help would be gratefull received.
William Wood, July 2006
Hi, just remove the diaphragm and check for holes, but don't forget to turn the mains water supply off as well as the electric first!

Paul, July 2006