Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

about glow.worm.fuelsaver f?

control model ep3002 when running central heating setting manually both sliders have to be in on position why can't i run central heating slider independently could it be the hot water thermostat and room stat.are wired wrong causing the water stat to override the room stat or...........
george.e.manchester, November 2010
your wiring is done on 10 program either your system is gravity hotwater ot wiring in correct or clock set to hotwater piority, it can be changed with setting behind clock

k, November 2010
Depends on the system, regardless of timeswitch and boiler.
If the system is gravity, the water needs to be on to fire the boiler while the ch runs the pump, possibly through a roomstat.

Carefree, November 2010