andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

baxi 105e pressure exceeds 3 bar?

My baxi boiler keeps going up tp 3.5 bar pressure when i put the heating on even though the pressure is only at 1 bar when cold. Can anyone tell what the problem is ?
steve, December 2010
Expension vessel faulty, fill pressure to 1 bar when system pressutre to zero, and if fault continue than add another vessel to heating system elsewhere

k, December 2010
either pipe to pressure vessel is blocked, the vessel needs to be repressurised or the vessel faulty

brian, December 2010