1 hour ago mike asked ... F+p 913t dishwasher?    |    Emma asked ... Foot pedal smoking?    |    Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Click here to ask your question

volkera linear 28?

hi have problems originally lossing presure constantly replaced pressure release valve redudced to a slow drip think there could be problems with expansion vessel can anybody tell me what the setting is for the pressure in vessel or any advice
john, December 2010
when cold pressure to be 1 bar than check if pressure rise when heating on than is vessel. or if still leaks only on hotwater than something else need further check require

k, December 2010