Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Incorrect system water pressure?

We have just had a new Ferroli optimax he plus 31 c fitted. the error code F37 has come up which I believe means the pressure is too low in the system. How do I fill the system to get the correct pressure, any help much appreciated.
Tony, December 2010
Normally near the base of the boiler there is a steel braided pipe which feed the boiler with cold water to pressurise the system. This will have a small 90 degree tap on it (bit like a washing machine tap)

Close by there should be a small pressure gauge. By opening the tap very slowly you should see the needle on the gauge go up when it reaches 1.5bar turn the tap off.

If you exceed the pressure it can be reduced by bleeding any of the radiators. Hence this also means that if you bleed radiators you will need to reset system pressure.
If you are still not certain then ask the person who installed the system to help.

M, December 2010
Thanks for the link, however I am not very technically minded and wondered if anyone could explain in laymans terms