Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

how can i solve this problem?

Vaillant eco TEC boiler F22 problem?

i have a vaillant boiler and just now i used the kitchen tap water and there is not hot water. And, the boiler is flashing F.22 and i don't know what this means! and the pressure has dropped to 0.2 and i have read the installation booklet, but it doesn't help me. How to i fix this problem?? than
kamila, February 2011
If it is an Ecotec plus, there are two grey handles underneath the boiler one on the left and one towards the middle, both will read 'closed' on them as you look at them.
Open both slowly (1/4 turn), the water will start to enter to re-pressure the boiler. while watching the guage (right hand corner of the boiler), until it is into the grey area, then turn BOTH back off.
Press the minus ( - ) button under the display, this will give you a reading in terms of bar pressure as to how much pressure is in the boiler, once it is reading 1 to 1.5 bar you are where you should be.
Then press the boiler reset (above the minus button) and things should return to normal.

Carefree, February 2011
re-pressurise boiler to 1-1.5 bar

brian, February 2011