Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

How can i resolve intermittent hot water?

My vokera combi boiler has a problem. Diaphragm ok, pressure within boiler ok, but when I turn the tap/shower/bath on the flame flares up and then subsides after 10sec. Replaced thermister but not cured? could it be PCB?
mel, February 2011
Vokeras of a certain age had issues with the flue venturi, slightest build up of dirt causes the classic hot/cold/hot cycling. If you can handle a multimeter, have the service manual and know there are mains voltages involved, you can monitor the state of the flue venturi pressure switch when the boiler cuts out. You need to take the venturi out to clean it properly, as its in the combustion chamber one is obliged to say this is a job for a corgi man, in case you gas your family with carbon monoxide.... It could just be the differential switch in the flue is signalling a real blockage.... but my guess is it just needs cleaning.

c, February 2011
could be c/h thermistor or h/water heat exchanger needs cleaning

brian, February 2011