Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

renewell of manifold?

the plastic manifold in the worcester bosh greenstar 25/ 30 has had to be replaced due to a defect in the sidewall of this componant resulting in a leak through a pinhole. i have replaced the £14.35. plus vat manifold at great expense. i would like to know why this happend and is there anything that con be done to avoid another leak. the boiler is 5 yrs old.
kev, April 2011
This is a very common problem with this boiler. The nice people at Worcester deny there is a fault with this manifold but I personally have change countless numbers of them.

The only thing that could possibly help, is to fit a water expansion vessel on the cold main as it enters the boiler. If you read the installation instructions, positioning is detailed in there.

Unfortunately however, it seems that this is just a badly designed manifold and you may have to resign yourself to changing the part every few years.

Carefree, April 2011
link Click here to see other fixes for Worcester.