narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

preasure valve?

the u shape preassure pipe situated on the outside wall seems to have a constant dripping how do i stop this the preasure in the boiler is normal
chris, May 2011
the preasure is normal at all times just this constance drip from theo utside ubend pipe

chris, May 2011
pressure relief valve passing/leaking
does this only happen when CH on?
has system been overpressurized recently?
whats the pressure gauge read when system cold?
whats the pressure gauge read when system hot?
sounds like your pressure relief valve needs replacing
& expansion vessel needs checking [possibly recharging]

manwithnoname, May 2011