tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Jerry asked ... Alpine 7287?    |    Guy asked ... Gaggenau fridge alarm problem?    |    mike asked ... Fisher & Paykel 913t dishwasher?    |    Emma asked ... Foot pedal smoking?    |    Click here to ask your question

Worcester 24i constant repressuring?

Worcester 24i, 2 yrs old, needs repressuring every week. Fitter says this is normal. Warranty expires very shortly. Does anyone else have a problem or do I have an undectected leak?
Janmaz, September 2011
your boiler needing repressurising every week normal!!!!!!!! i think not mate!!!your installers a mug and he's taking you for one!! pressurised boilers should only need topping up 2-3 times a year,max, unless there is a leak on the boiler,pipework or radiators, or you bleed a radiator.
you need to check all radiators to see if there's a leak,and also the 15mm copper pipe going to outside, boiler manufacturers will not uphold warranties if it is down to installer error or leaks on the system.
get a 3rd party to investigate

Stephen, September 2011
link Click here to see other fixes for Worcester 24i.