andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

baxi 105e safety valve opening,too much pressure?

central heating on, pressure increase to over 2.5bar causing relief valve to open,Is the safety electrical swiches faulty?
gaz-t, September 2011
checked pressure in expansion vessel this was very low, increased pressure as requested boiler working as it should per manual.thank you.

gaz t, November 2011
Your boiler expension vessel faulty, try fill air to 0.9 bar and see if improve ot fit another one of 24 litre expension vessel on any heating pipe , can be fitted any where