Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

What is problem with Pressure on Vaillant Boiler?

I have a Vaillant Eco Tec Plus Combi boiler (5 yrs old) that works fine -but- I notice that the water pressure falls to zero when not working and when CH is on, the water pressure inreases steadily to 4 bar and stays there until CH is Off. There is also a steady dripping of water from the blow off pipe. Is this a problem with the expansion tank or the blow off valve
Ron, October 2011
faultcode f 32 fan not working

max, June 2012
It is not a problem with either, it's both, you need to re-pressure the expansion vessel to a charge of about 0.8bar (the boiler water must be able to escape the vessel while charging), then you will most likely have to change the prv.

Carefree, October 2011
As the valve is leaking, faulty. replace, that will stop your pressure drop.

SD, October 2011