Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Whats the probem with my Stelrad Group - Ideal Sprint F Combi?

The problem is with the hot tap water side of the boiler, (the central heating works fine all the time). When a hot water tap is turned on the boiler fires up, (or increases the gas if the central heating is already on), then runs for 2 or 3 seconds and then turns the gas, (or extra gas), off. It then cycles through this by starting up, (or increasing the gas), and stopping, (or reducing to just the central heating amount of gas).

So in essence once the water is turned on and the boiler fires up there is something monitoring the system and shutting down the tap water heating part only. Any suggestions would be greatly appreciated.
Ross, October 2006
how do i set my timer on my boiler

mrs s crawley, November 2012
fan won't work every summer have this problem

sam, June 2009
the rubber diaphragm in the diverter valve has deteriorated and is letting water pressure escape past the diaphragm and is not maintaining enough pressure on the microswitches. The initial surge of pressure is enough to initiate ignition for the hot water but after a few seconds line pressure normalises and the diaphragm relaxes, breaking the electrical circuit.

Josh Hooker, August 2008