narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

bar pressure wont stop rising when the system is turned on?

how can i fix it ?
Declan, January 2012
the expansion tank in your boiler needs to be replaced it all depends the make and model of your boiler how difficult it is as some have to be taken off the wall

annon, January 2012
It will only go to 3, An overpressure release valve will then open, if it is going up that much, water getting into system, check fill loop valve, make sure it is turned off fully. Normal pressure cold system, usualy 1 bar, above that it could go to 3 on heating, depending on system size, If it has just started doing it, drain boiler down, make sure that expansion vessel is empty, refill system, If water filsl expansion vessle, no buffer for water expansion, so pressure will go up high