andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

boiler only runs with coverplate open?

hi
have a vokera excell 80sp combi boiler .boiler only runs when coverplate off or slightly adjarred.soon as plate secured boiler cuts out any ideas ?
martin, January 2012
remove fan and clean impeller blades of dust build up. Clean fan venturis (part that the air pipes from the air pressure switch connect onto fan)

The master, January 2012
checked that pipe and it is clear

martin, January 2012
By removing the heatshield you are allowing the boiler to breath.There is a large bore pipe,only about 4ins long.This is known as a ventura.Air is drawn into the boiler through this pipe.Sometimes this ventura needs cleaning out.

paul, January 2012