Dot asked ... Russell hobbs?    |    Jon asked ... How do I remove the flywheel. Mountfield 1640h ride on mower?    |    Keith Mumby asked ... Fordson starter solenoid?    |    Suzanne asked ... Washing programme stops after 3 minutes?    |    Rif asked ... Kenwood Dishwasher KID60S20 leaking from front?    |    Click here to ask your question

error code 119?

error code 119 on a potterton boiler, boiler pressure, manual not helpful. Advice please
peter, February 2012
NO model, so difficult.

usualy pressure error, refers to Low pressure, check gauge, should read about 1 bar cold, less, top up system using fill loop, (its the valve on a flexible metal braid pipe, connected near to boiler) If it is going over pressure, pressure release valve will operate, at 3 bar, so will not give error.

SD, February 2012