David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Freya asked ... Frister & Rossman Cub7 Sewing Machine?    |    katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Click here to ask your question

Problem refilling CH system after fitting Grundfos 15-50 130 selectric pum?

I have had to drain my CH system to fit a new radiator. Problem occurs when refilling.It only takes about 25% of the normal amount of water to fill it before it backs up to the header tank. There seems to be no water getting to the manifold and to the radiators via the smallbore pipework. Have tried firing up the sytem briefly to see if pump will circulate the water but no go.Hot water only seems to be reaching the pump and no further. Is there a switch or a valve on the pump that has locked off and can it be reset?
Wispering Ted, February 2012
On the end of pump, a large screw, its a plug, unscrew, you will get some water out, but you will then be able to make sure pump can turn. Are you bleeding the radiators.

SD, February 2012