GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Why is red light still flashing?

My heating and hot water are working but the red light on low pressure system is still flashing? I have an elderly father and young daughter in the house and do not know what to do? Is this dangerous?
Ranjana! From Manchester!, April 2012
The name of boiler is swift!

Ranjana!, April 2012
If it is low pressure, you need to increase the pressure, should read about 1 bar when the system is cold. Not dangerous, but very surprised your system is still working, most cut out. Somewhere close to the boiler, will be a fill loop. A flexible metal braid pipe, with a valve on it. as long as both ends of that pipe are connected, open the valve to fill boiler. VERY slowly. increase pressure to 1 bar, or if no dial, until light goes out. IF the pressure drops again in a short period of time, you have a leak on the system, and need to get that seen to. You have not given the make or model number, which would of helped me.

SD, April 2012