Suzanne asked ... Washing programme stops after 3 minutes?    |    Rif asked ... Kenwood Dishwasher KID60S20 leaking from front?    |    Fraser asked ... Spares for power craft ppcs 38cc?    |    FB asked ... Toyota Yaris Speed Camera Warning Beep?    |    Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Click here to ask your question

vokera boiler problem?

compact 24 central heating pressure gauge rises when domestic hot tap open + water flow from overflow when i open a rad to drop pressure to 1 bar then close pressure rises to 3 bar again
richard, May 2012
vokera compact 24
GCN 47-094-??
pressure keeps rising & leaks from PRV overflow?
first of all make sure your filling loop valves are closed fully
take filling pipe off & check for drips from valves
with filling pipe removed if pressure still rises chances are the pipe in pipe heat exchanger is pinholed & needs replacing
test for pinholed heat exchanger by turning OFF cold water inlet to boiler
if pressure stabilizes then heatex definitely pinholed

manwithnoname, May 2012
When are you doing what.
ARE you setting to 1 bar, WHEN the system is cold? Pressure will always rise. Set to 1 bar when cold, should not reach 3 bar, unless a blockage somewhere, check valves etc on boiler

SD, May 2012