Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Leak on feed side of radiator on a pressurized combi system?

I have a small leak from the valve joint on the feed side of a radiator, so the system which has halstead combi boiler is losing pressure. Do you have to drain the system? and if so whats the procedure? Thanks
Peter, October 2006
drain the system from a radiator with a drain tap fix the valve repressure the system use the filling loop on the boiler to about 1.5 bar bleed the rads not letting the pressure go below 1.0 bar.

hi-spec plumbing, October 2006