GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Ferroli HE 31c optimax code F37?

I have just put a new PCB in and have reset the boiler my pressure gauge is 1.5b but i still have the fault any ideas, the pressure switch is OK as i did not have this fault on the old PCB
gj, August 2012
ok got the difinitive answer now so anybody in future will know.
the PCB covers 2 models, HE31C and the HE31C plus. for the HE 31C to run correctly there is a parameter that needs to be changed. phone the ferroli tech helpline and they will talk you through it.

paj696, August 2012
ok if you take the plug off the pressure sensor and bridge out the first and the last wire positions on the plug with some wire then switch the boiler on. if it fires up ok then you need to replace the sensor.i did this last night pick up new sensor today from PTS.( DONT KNOW IF THE THE BOARD GOING BLEW THE SENSOR OR VISA VERSA)

PAJ696, August 2012
snap i to am having the exact same problem. anybody out there got an answer~?

paj696, August 2012