GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

I recently repaired a leak on a rad valve, ?

I recently repaired a leak on a rad valve, where some of the system was drained. The system is 0.7 bar cold and when fully operational it goes in the red, could there still be air in the system causing this. It's a combi boiler, glow worm, about 7 years old. Could you please advise me. Many thanks
JJ, January 2013
also check u havent left any boiler valves closed

kash, January 2013
expanssion vessel needs inflating on the boiler. drain down the system, then get a car pump and inflate the tank to 1.5bar. its the red tank fitted to the rear of the boiler it has a car tyre type inflating valve fitted to it it will be on the top or bottom.

kash, January 2013