Michelle asked ... How can I fix a error?    |    Tusch asked ... Fisher & Paykel Smart Drive 9 Pride 5.5 Model MW05559AU FP WH?    |    Dwayne B. asked ... Intermittent (twice) Then Complete Loss of Power?    |    Aunt Bee asked ... Bernina Update 1630 work light not working?    |    Larry asked ... Hybrid Weed wacker not working with battery?    |    Click here to ask your question

how can i fix my brittony combi se?

I set the water pressure on my brittony combi se at 2 bar and when the heating is on the water pressure expands over the blow off limit of 3 bar . When the CH is off the water pressure settles below 1 bar which wont allow the boiler to function, and new water has to be added to get above 1 bar and start up the boiler. The gas fitter I use has within the last couple of months fitted 2 new water pressure release valves but to no avail . Anyone any ideas?
Peter Lawn, November 2006
no pressure in expansion vessel. open the schrider type valve (if spelt correctly!!) on the vessel, if water comes out then new vessel needed, if air comes out then needs pressurising.

gavgas, October 2007
check the expansion vessel!!

me, December 2006