Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Vaillant VCW GB 242 EH, cuts out when upto temp?

My Vaillant VCW 242 EH cuts out when upto temperature. When its fires first time it stays on for 2-3 minutes, then nocks off (doesn't trip), when it fires back up it stays on for 20seconds then nocks off again. This process then repeats itself. I've replaced the flame supervision PCB, also the NTC resistor. I've got a Flame sensor electrode on order. Does anybody what it could be if its not the electrode?????????
Simon Richardson, November 2006
This is not an electrical problem. Sounds to me like it is modulating from high gas to low gas then off, when it's cooled down a little it repeats this. This is due to a circulation problem, mucked up system/sludge/blockage/slow running pump etc.... These boilers are very relyable but most engineer don't know much about them so instead of attempting to repair them they quote for a new appliance. Best advice is to get someone that has experience with this boiler. Hope that helps!

Andy, heating engineer., December 2006
Might be filter on return pipe at boiler is partially blocked. Had same problem with Baxi and this fixed problem.

Houston, November 2006