2 hours ago Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    Click here to ask your question

Radiator problem?

Can anyone tell me why when my gas ch system is set to hot water only the upstairs radiators come on too (this hasn't always been the case ) ?? Thanks.
Steve, February 2013
Yep that's it thanks you're a star

Steve, February 2013
There's a motorised valve - it can direct the heated water to taps or radiators or - in the middle position - to both.

Sometimes the valve gets stuck.

http://www.wickes.co.uk/3-way-mid-position-valve/invt/443033/

Peccavi, February 2013