GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

dripping boiler?

I have a healstead Ace boiler and the pressure keeps going too high and it is now leaking - or dripping water out!! the heating and the hot water is still working but its a bit loud?! any advise anyone??
little till, March 2013
hi the pressure is to high on the boiler so it dripping water out the safety valve outside. this i s the reason for the drip. its also for the loud banging sound as when it throws water out and goes to close it has a spring which causes the sound. now what u need to do is first stop the pressure rising it either
1. u have left the filling loop open.
2. the filling loop is faulty and constantly letting water through.
3. there is a hole in the dhw heat exchanger causing the mains water to enter the central heating water.
there pressure should be around the 1.3 bar. fix the problem and every thing should be fine. u may need to change the driping valve if it keeps leaking after u have fixed the problem

kash, March 2013
link Click here to see other fixes for Ace.