GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Can anybody advise why Flexicom 35CX goes into state S53 when in DHW mode?

The boiler works fine for central heating and DHW for sink taps and shower, but when bath tap is used the boiler first starts at a high rate then goes into low rate mode,waiting time mode S53, so the bath tap water starts at normal temperature then runs cold as boiler goes into low rate. The book says due to difference flow/return sensor to high so have checked thermistors, connections and refit them to pipework using heat conductive contact grease. But to no effect. I would appreciate any advice/guidance.
bigal, March 2013