Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Click here to ask your question

Y Plan - Mid Position Valve 'fault'?

Hi, I have BGMVSP-23 'mid position' valve.

(I believe a Y plan setup)

Basically the pump only runs when the cylinder calls for it.

The valve appear to do all the right things, i.e.:

CH H
HW W
CH&HW M

So 2 issues:
1. It's just that when only the CH is on, the pump doesn't run / boiler doesn't fire
2. IF both are on, initially everything fine (valve in M position, rads hot), however once the cylinder is up to temp, the pump switches off - so you end up with a cold house, even when the CH is set to continuous on the programmer and the Room stat is asking.

As I understand it, there are two switch wires - white & grey, and if either is live they should make the orange live to run the pump?

So is it the programmer faulty.

Or the microswitch in the actuator

Thanks for any help.
Graham, November 2013
What you need to do is set programmer to c/heating only
then
a; check if there's power to the white wire on valve assuming stat is calling
b; with valve in mid position the orange wire should be live if not its the micro switch
c; if there's no power to white wire which is usually on connector No 5 check connector No4 which is feed from programmer to stat
In other words all things being equal you should have power to connector No 4-5 and 8

toptrish, November 2013